ISRO Electrical Engineering (EE) 2014 - Question 32

All ISRO Electrical Engineering (EE) papers | ISRO Electrical Engineering (EE) 2014

For an unbalanced fault with paths for zero sequence currents, at the point of fault

  • A. the negative & zero sequence voltages are minimum
  • B. the negative sequence voltage in maximum & zero sequence voltage is minimum
  • C. the negative sequence voltage in minimum & zero sequence voltage is maximum
  • D. the negative & zero sequence voltages are maximum

Answer: D. the negative & zero sequence voltages are maximum

Explanation: At the fault point, the fault acts as the source of negative and zero sequence currents; hence negative and zero sequence voltages are maximum at the fault point and decrease towards the source/neutral.