What is the approximate value of the surge impedance loading of a 400kV , 3-phase 50Hz overhead single circuit transmission line
- A. 230 MW
- B. 400 MW
- C. 1000 MW
- D. 1600 MW
Answer: B. 400 MW
Explanation: SIL = V²/Zc = (400 kV)²/≈400 Ω ≈ 400 MW.