Topic: Refrigeration and Air Conditioning
The Sensible Heat Factor (SHF) of a cooling coil is 0.75. This indicates that:
- A. 75% of the total heat removed is latent heat
- B. The ratio of sensible cooling to total cooling is 3:4
- C. 25% of the total heat removed is sensible heat
- D. The bypass factor of the coil is 0.75
Answer: B. The ratio of sensible cooling to total cooling is 3:4
Explanation: The Sensible Heat Factor (SHF) is defined as the ratio of Sensible Heat (SH) to Total Heat (TH), where TH = Sensible Heat + Latent Heat. An SHF of 0.75 means that $\frac{SH}{TH} = 0.75$, which is equivalent to the fraction $\frac{3}{4}$. Therefore, the ratio of sensible cooling to total cooling is 3:4.