A 3 phase induction machine draws 1000 kVA at a power factor of 0.866 lag. A synchronous condenser is connected in parallel to draw an additional power of 750 kVA at a leading pf of 0.707. The power factor of the total load supplied by the mains is
- A. 0.95 lag
- B. 0.99 lead
- C. 0.90 lag
- D. 0.95 lead