ISRO Electrical Engineering (EE) 2018 - Question 43

All ISRO Electrical Engineering (EE) papers | ISRO Electrical Engineering (EE) 2018

The distribution system indicated below is to be protected with overcurrent protection. Identify the locations where essentially directional overcurrent relays will be required considering proper fault discrimination. [Figure description: A single-line diagram. Bus-1 (left, fed by a Grid) connects through breaker Br-1 along a horizontal line to breaker Br-2 which connects to Bus-2 (centre). From Bus-2 another breaker Br-3 continues along the line to breaker Br-4 and Bus-3 (right, fed by another Grid). From Bus-2 a feeder goes down through breaker Br-6 and then through breaker Br-7 to Bus-4 (fed by a third Grid). Also from Bus-2, breaker Br-5 feeds a Load. So there are three grid sources (at Bus-1, Bus-3 and Bus-4) and one load fed via Br-5.]

  • A. Br-1, Br-4, Br-8 and Br-7
  • B. Br-2, Br-3, Br-5 and Br-6
  • C. Br-2, Br-3 and Br-6
  • D. Br-1, Br-4, Br-7, Br-5

Answer: C. Br-2, Br-3 and Br-6

Explanation: Breakers Br-2, Br-3, and Br-6 feed directly into Bus-2 from parallel tie lines/grid sources; they require directional overcurrent relays pointing into their respective lines to discriminate internal from external faults.